The system works via pex pipe a small pump a water heater and a thermostat.
Concrete slab insulation for radiant heat.
The concrete was 4 thick and the insulation under the slab was 2 thick.
Slabs that include embedded hydronic tubing for radiant heat always need a continuous layer of horizontal insulation under the entire slab.
When the thermal mass of the concrete is heated the warm slab acts as a radiator distributing even heat throughout the structure.
Need insulation for under concrete slabs slabs with radiant heat.
Designers generally insulate both directly under the slab and around the perimeter as well.
While it was done as a new house was being built in my last house i poured a concrete floor on top of a wood framed floor system and could have put radiant heat in that as well.
It s possible to calculate the r value needed to meet this goal while accounting for such factors as floor coverings soil temperature and required upward.
How much insulation is necessary under a typical radiant slab.
The foil within the product acts to spread out the heat signature of the heating coils.
It serves on top of those purposes mentioned above also as protection for the concrete slab itself and prevent its earlier disintegration due to oxidation from soil gases and chemicals.
Any cooler surface in contact with the slab will try to steal its heat.
The reflectix concrete slab insulation is an innovative easy to handle product that increases the energy efficiency of radiant floor and snow melt systems under concrete.
Insulationstop is the best source for top quality products at the best price.
Because heat goes to colder areas radiant floor insulation is almost all the time placed under the heating element often the concrete slab.
John siegenthaler a consulting engineer who specializes in hydronic heating system design responds.
Rfoil 2222 series reflective r 13 0.
Downward heat loss from a radiant slab should not exceed 10 percent of upward heat output a ratio derived from european installation standards for floor heating systems.
Remember that your slab will be about 75 degrees f.
If you re pouring up against your foundation walls insulate between the slab and the walls.
If your slab is heated it s a good idea to increase the r value of the vertical and the horizontal insulation to at least r 20.
Crete heat r 6 or r 10.
Mainly heated slabs radiate outward rather than downward so insulation on the edges of the slab is most important.
The picture above shows a concrete floor we re about to pour with radiant heating tubes installed.
Many increase the under slab insulating foam board thickness to 3 or 4 inches at the outer 2 to 4 feet of the slab.
We stock rfoil and crete heat insulation brands for use in concrete slab and between the joists pex radiant heating installations.